Honeywell MAXPRO Intrusion MPIP2000U/3000U Series Installation and Setup Guide
800-23044 Rev. A draft_11 15
Feature MPIP2100U MPIP3000U
Access 10,000 10,000
Programming
Schedules 50 100
Holidays (per year) 40 40
Controller rules 50 100
Bus Network
On-board IB2 data bus lines 1 2
On-board V-Plex sensor bus lines 1 2
Power Supply
Max. constant current 3.0A 3.0A
Battery charging capacity
1
36Ah 36Ah
Communication Paths
IP/Ethernet 1on board 1on board
Radio communication (4G/LTE) Optional Optional
Central Station Signalling Protocols
ContactID
SIA
AlarmNetvia AlarmNet services
2.2.2 Inputs and Output
l Provides 10 on-board hardwire zones.
l Supports up to 16 two-wire smoke detectors on zones9 and10 (32 in
total).
l Four-wire smoke detector reset through use of on-board relay.
l Low-voltage trigger outputs.
l Outputs can be programmed to activate in response to system events
(alarm condition), or at a specific time of day, or manually.
l Provides up to three emergency keys on the keypads (configurable per
area).
l Battery sensing hardware that monitors two batteries independently and
can sense when either battery voltage is too low. Prevents deep discharge
from occurring.
1
With the MPI medium-sized cabinet (MPIBXM35), you can use a battery capacity of up to
18 Ah. If you need more battery capacity, you need to install a second tamper-protected
cabinet with the second battery.