EasyManuals Logo
Home>Honeywell>Security System>Notifier DVC

Honeywell Notifier DVC User Manual

Honeywell Notifier DVC
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #31 background imageLoading...
Page #31 background image
Mass Notification — P/N LS10063-000NF-E:E 06/26/2019 31
Programming Programming
Create Fire Logic Zones
The logic equation for the Fire Active Tone sequence must reference all DVC, panel, and NCA-2 nodes on the network. Write an OR
logic equation that includes the local DVC’s general zone, the general zones on the other networked DVCs, and the general alarm zones
on the networked fire panels. The example in Figure 3.20 assumes a network with two DVCs, three fire alarm control panels, and one
network control annunciator.
Figure 3.20 Create a Logic Equation to Activate Fire Active Tone
Add Fire Logic Zones to PAM Programming
On the PAM Settings branch:
1. Map a common general zone (for example, Z1) to all the PAM points designated as the Fire category. Select PAM View “All CBEs”
for quick data-entry.
1. Select “OR” as the function.
2. Select Zone Z1.
3. Select Zone Z1 on networked DVC nodes.
4. Select Zone Z0 on networked FACP nodes
and network control annunciators.
5. Close the equation with a parenthesis, and
save changes.
6. Add label “Fire Active Tone” (optional).
7. In this example, In this example, ZL3 is the
Logic Zone programmed for activation of the
Fire Active Tone.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier DVC and is the answer not in the manual?

Honeywell Notifier DVC Specifications

General IconGeneral
BrandHoneywell
ModelNotifier DVC
CategorySecurity System
LanguageEnglish

Related product manuals