EasyManuals Logo
Home>Honeywell>Repeater>Notifier IDR-2P

Honeywell Notifier IDR-2P User Manual

Honeywell Notifier IDR-2P
41 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
IDR-2P, -2A & -6A Repeaters User Manual
Commissioning
16997-411-000-9, Issue 9
March 2008
3 Commissioning
This section gives the procedure for
commissioning the IDR repeater.
Commissioning consists of:
a. Preliminary checks.
b. Power-up checks.
3.1 Preliminary Checks
Carry out the following preliminary checks for
EVERY IDR repeater being commissioned,
prior to powering-up the system:
1 Check that all cables brought into the IDR
repeater have been terminated correctly.
The connection of external wiring is
described in Section 2.8.1. All power and
signal cabling and wiring must conform to
the appropriate local regulation.
2 Check that the address has been set
correctly as described in Section 2.8.2
(RS485 network) or Section 2.8.3 (ID
2
net
network).
Only terminate the IDR
repeater power cables at
the fire control panel
after ALL preliminary
checks have been done.
ATTENTION
Observe precautions for
handling Electrostatic
Sensitive Devices

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Notifier IDR-2P and is the answer not in the manual?

Honeywell Notifier IDR-2P Specifications

General IconGeneral
BrandHoneywell
ModelNotifier IDR-2P
CategoryRepeater
LanguageEnglish

Related product manuals