IDR-2P, -2A & -6A Repeaters User Manual
Operation
22997-411-000-9, Issue 9
March 2008
4.3.3 Pushbutton Test (-2A)
Press each pushbutton in turn. Verify that:
a. The buzzer beeps.
b. The LCD displays the name of the
pushbutton.
c. The corresponding LED as shown at the
left illuminates.
Turn the keyswitch to access level 1 to exit
the test.
AND AS FOLLOWS:
PUSHBUTTON ILLUMINATES LED
TEST
DELAY ACTIVE
SYSTEM FAULT
COMMUNICATIONS LOSS
MUTE BUZZER Upper General FIRE
ACCEPT Lower General FIRE
EVACUATE Upper General FAULT
SILENCE SOUNDERS Lower General FAULT
RESOUND SOUNDERS DISABLEMENT
RESET POWER