3. If installed, disconnect the tube set.
4. Disconnect all peripheral cables from the server.
5. Remove the server:
a. Loosen the release lever thumbscrew (callout 1).
b. Use the release lever to pull the server out of the bay (callout 2).
6.
Place the server on a flat, level work surface.
Extend the chassis from the rack
WARNING: To reduce the risk of personal injury or equipment damage, be sure that the rack is adequately
stabilized before extending a component from the rack.
Prerequisites
Before you perform this procedure, make sure that you have a T-25 Torx screwdriver available.
Procedure
1. If the chassis has a DLC-enabled server installed—a server that uses a cooling loop instead of a heatsink—do the
following:
a. Power down the servers.
b. Disconnect each power cord from the power source.
c. Disconnect each power cord from the chassis.
Removal and replacement procedures
28