Figure 5-13 Connecting DC power cables
----End
During DC input power cabling, leave at least 50 mm of slack. The axial tension
on PV connectors must not exceed 80 N. Radial stress or torque must not be
generated on PV connectors.
5.5.3 Connecting Cables to Staubli MC4 Terminals
Use the Staubli MC4 positive and negative metal terminals and DC connectors
delivered with the inverter. Using incompatible positive and negative metal
terminals and DC connectors may result in serious consequences. The resulting
device damage is not covered by the product warranty.
SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual 5 Electrical Connections
Issue 18 (2024-03-10) Copyright © Huawei Technologies Co., Ltd. 51