Parameter Description
Current adjustment interval Value range: [1, 5s]
You are advised to keep the default value. A larger
value indicates a lower current adjustment speed.
If this parameter is set to 2s and the current at the grid
connection point exceeds the threshold, the inverter
adjusts the current every 2s.
Note a: If the inverter shuts down because the feed-in current adjustment is not complete within
the specied time, the user needs to manually start the inverter. By default, the number of
manual startups cannot exceed three within 30 days. If this limit is reached, it is not allowed to
manually start the inverter again.
Note b: If the maximum feed-in current is not adjusted to a value within the range limit within
15s, the inverter will shut down and report a Power Control Abnormal at Grid Connection Point
alarm.
----End
7.3.2.2 Scenario Where the App Connects to the SmartLogger
If multiple inverters are cascaded, the SmartLogger must be used.
Procedure
Step 1 On the home screen, choose Power adjustment > Feed-in at limited current.
Figure 7-7 Feed-in at limited current
SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual 7 Human-Machine Interaction