H Battery Capacity Test
Context
A deep discharge test method that tests the battery real-time capability and long-
time backup capability after batteries have not experienced deep discharging for a
long time.
NO TICE
Before a capacity test, ensure that:
The UPS is working in normal mode; oat charging or hibernation has lasted
for 2 hours after the state of charge (SOC) reaches 100%.
The UPS has generated no battery overtemperature, overvoltage, or overcurrent
alarm. No generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is
generated.
UPS2000-G-15KRTL-01/UPS2000-G-20KRTL-01: The load rate ranges from 5%
to 100% and the load
uctuation does not exceed 10%.
UPS2000-G-6KRTS/UPS2000-G-10KRTS/UPS2000-G-15KRTL/UPS2000-
G-20KRTL: The load rate is 20%–80% and the load uctuation does not exceed
10%.
Procedure
Step 1 Check the battery status for test start conditions.
1. On the Main Menu screen, choose Status and click
. On the Status
screen, locate Battery Status.
Figure H-1 Battery Status menu
UPS2000-G- (6 kVA-20 kVA)
User Manual H Battery Capacity Test
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 180

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals