Item Description Default
Value
Value Range
Bypass
mode
Set the output dry contact associated
with bypass mode. When the UPS is
in bypass or ECO mode, this dry
contact is enabled.
Dry
contact
3
Dry contacts 1–
6
Batt.
underv
olt
Set the output dry contact associated
with low battery voltages. When the
system battery voltage is low, this
dry contact is enabled.
Dry
contact
4
Dry contacts 1–
6
BPS
backfe
ed
Set the output dry contact associated
with bypass backfeed. When a bypass
backfeed alarm is generated, this dry
contact is enabled.
Dry
contact
5
Dry contacts 1–
6
Faulty
UPS
Set the output dry contact associated
with UPS faults. When a critical
alarm is generated, this dry contact is
enabled.
Dry
contact
6
Dry contacts 1–
6
4.6.3.3 System Parameters Screen
Parallel screen
Figure 4-28 Parallel screen
Table 4-18 Parallel settings
Item
Description Default
Value
Value Range
Single/Parallel Species whether the UPS
works in single mode or
parallel mode. This
parameter is congurable
only after the inverter is
shut down.
Single Single, Parallel
Redundant UPSs Set the number of redundant
UPSs. This parameter is
congurable only after the
inverter is shut down.
0 0–3
UPS2000-G- (6 kVA-20 kVA)
User Manual 4 Control Panel
Issue 18 (2021-07-16) Copyright © Huawei Technologies Co., Ltd. 60

Table of Contents

Other manuals for Huawei UPS2000-G-10KRTL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-G-10KRTL and is the answer not in the manual?

Huawei UPS2000-G-10KRTL Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-G-10KRTL
CategoryUPS
LanguageEnglish

Related product manuals