EasyManuals Logo
Home>IBM>Server>iSeries Series

IBM iSeries Series User Manual

IBM iSeries Series
512 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #436 background imageLoading...
Page #436 background image
- Power supply P02 (dual line cord)
- Power supply P03 (single line cord)
- Power supply P03 (dual line cord)
For FC 5078, FC 0578, FC 5088, or FC 0588, perform “Power PIP8” on page 168 to isolate the
failing item. The failing item may be one of the following parts (see Type, model, and part
number list for part number).
- Any part on the expansion bus.
- Power supply P01
- Power supply P02
This ends the procedure.
6.
Is the SRC 4414?
v No: This ends the procedure.
v Yes: Perform “Power PIP6” on page 160 to isolate failing item. Then, return here and continue with
the next step.
7.
Is the SRC 4414 still present?
v Yes: Replace the battery power unit charger (see Type, model, and part number list for part
number).
This ends the procedure.
v No: Continue with the next step.
8.
Power on the system. Does the expansion tower that was failing, power on?
v No: Go to “Starting point for all problems” on page 2.
v Yes: Continue with the next step.
9.
Remove the ac line cord from the outlet. Does a battery power unit, charger fault occur?
v Yes: Replace the battery power unit charger (see Type, model, and part number list for part
number).
This ends the procedure.
v No: This ends the procedure.
Instructions for Models 830, 840, SB2, and SB3
1. Is the SRC 1xxx 1810, 1820, 1830, or 1840?
v No: Continue with the next step.
v Yes: Perform Power PIP6 in Migrated Expansion Tower Problem Analysis, Repair and Parts
manual on the V5R1 Supplemental Manuals web site
to isolate the failing item. The failing item
may be one of the following parts (see Locations and addresses ):
Any part on the system bus
Power supply P01, P02, or P03
2. Is the SRC 1xxx 1B01, 1B02, 1B03, 1B04,1B05, 1B06 or 1B07 or 1B09?
v No: Continue with the next step.
v Yes: Use the following, except for FC 5078, FC 0578, FC 5088, FC 0588, FC 5095, or FC 0595.
Perform “Power PIP6” on page 160 to isolate the failing item. The failing item may be one of the
following parts (see Locations and addresses ):
Any part on the system bus.
Power supply P01, P02, or P03 (single line cord)
Power supply P01, P02, or P03 (dual line cord)
Use the following for FC 5078, FC 0578, FC 5088, FC 0588, and perform “Power PIP8” on page
168 to isolate the failing item. The failing item may be one of the following parts:
Any part on the expansion bus.
424 iSeries: iSeries Server 270, 800, 810, 820, 825, 830, 840, 870, 890, SB2, and SB3 Hardware Problem Analysis and
Isolation

Table of Contents

Other manuals for IBM iSeries Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBM iSeries Series and is the answer not in the manual?

IBM iSeries Series Specifications

General IconGeneral
BrandIBM
ModeliSeries Series
CategoryServer
LanguageEnglish

Related product manuals