40
Installation and Servicing
Section 3 - Servicing
SERVICING
3.9 IGNITION / DETECTION ELECTRODE REPLACEMENT / INSPECTION
3 mm
Straight edge
1. Remove the fan.
Refer to Section
3.6
2. Remove the ue manifold.
3. Remove the burner.
Refer to Section
3.7
4. When servicing the boiler inspect the condition of the
electrode and check the dimensions shown. If there is
damage to the electrode continue to follow steps below
for replacment.
5. Unplug the ignition lead from the electrode.
6. Remove the earth lead from the electrode.
7. Remove the 2 screws holding the electrode to the
combustion chamber.
8. Remove the electrode.
9. Fit the new electrode, using the new
gasket supplied. Check dimensions as
shown.
Refer to Section
2.30 & 2.31
Ignition /Detection
Electrode
Spark Gap
3.5 mm
Refer to Section
3.2
3.10 CLEANING THE CONDENSATE TRAP
CH
Flow
Gas CH
Return
Condensate
Drain
SCAN
for video
1. Pull o󰀨 the rubber pipe at the sump drain.
2. Turn the trap clockwise to disengage and lift to remove.
3. Clean and ll trap with water.
CH
Circuit
Drain
Trap
2
CAUTION: Keep trap upright when removing
PRV
Grommet

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEAL LOGIC+ SYSTEM2 S30 and is the answer not in the manual?

IDEAL LOGIC+ SYSTEM2 S30 Specifications

General IconGeneral
BrandIDEAL
ModelLOGIC+ SYSTEM2 S30
CategoryBoiler
LanguageEnglish

Related product manuals