Technical Data
Page Operating Instructions for Powador .-. TL_EN
ENEN
Technical Data
. Electrical Data
Input levels 30.0 TL3 33.0 TL3 36.0 TL3 39.0 TL3
DC MPP range from [V] to [V]* 350 ... 800
Operating range from [V] to [V] 200 ... 800
Starting voltage [V]** 250
Open circuit voltage [V] 1 000 (start to 950)
Rated current max. [A] 3 x 34.0
Max. power per tracker [W] 20,000
Number of strings 3 x 1 (M) / 3 x 4 (XL)
Number of MPP trackers 3
Polarity safeguard Short-circuit diode
*At DC voltages below the MPP range the maximum rated current reduces the maximum input power.
**For PV generators with MPP voltages below the MPP range of the inverter: set the start voltage in the menu.
Output levels
Rated power [VA] 2,000 27,500 30,000 33,300
Grid voltage [V] 230 / 400
Rated current [A] 3 x 36.2 3 x 39.9 3 x 43.5 3 x 48.3
Rated frequency [Hz] 50/60
cos phi 0.80 inductive to 0.80 capacitive
Number of feed-in phases 3
Distortion factor [%] < 3
General electrical data
Max. eciency [%] 98.0
European eciency [%] 97.8
Make current [A] / ON duration [ms] 98 / 4.4
Internal consumption: standby [W] < 30
Internal consumption: night [W] ~1.5
Feed-in starts at [W] 120
Circuit design IGBT, self-commutated, transformerless
Grid monitoring Country-specic
CE conformity Yes
Table 1: Electrical data