GB - 20
COMBICONTROL
et.09
data port password
Address 0309h
This parameter denes the write protection password for the COMBIVIS data port. The
programming of the password occurs only via the serial interface. Then this password
must be entered here again for write access via the data port. Error message "operation
not possible" is displayed in case of locked data port write access. Value 0 switches off
the write protection password.
et.10
gateway address
Address 030Ah
This parameter determines the IP address of the appropriate gateway. As soon as
a connection to IP slave address outside the own network shall be made by the control
program, this address is used. In case of doubt the gateway address to be adjusted can
be ask for by the network administrator.
et.11
subnet mask
Address 030Bh
The decision whether an IP slave address is outside of the own network is determined
with this mask. If this mask is 0.0.0.0 the standard masks are used depending on network
class A, B or C. In case of doubt the subnet mask to be adjusted can be ask for by the
network administrator.
et.12
data port response delay
Address 030Ch
This parameter adjusts the response delay for the Combivis-data port in ms. The network
utilization can be reduced by setting of higher values. A value of 0 enables the fastest
communication with the control, but a high network utilization is also generated.
et.14
Link state
Address 030Eh
Displays state informations for the Ethernet link.
et.15
Link mode
Address 030Fh
Determines the adjustments of the Ethernet interface. Fixed values or automatic recogni-
tion can be adjusted here. The additional clearlock value 32 activates a special behavior,
which corrects link problems automatically with automatic detection on both sides (control
and switch).
3.3.3 Real-time clock
The internal real-time clock is adjusted and/or read-out with the following parameters.
rc.00
time
Address 0400h
This parameter displays the time in hours and minutes in a 24-hours format. Writing on
this parameter adjusts the time.