EasyManuals Logo
Home>KEB>DC Drives>COMBIVERT F5 Series

KEB COMBIVERT F5 Series Installation Guideline

KEB COMBIVERT F5 Series
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
36
Installation and Connection
3.3 Connection of Power Circuit
3.3.1 Terminalstrip X1A
Terminal strip X1A / 230 V - class
suitable for
180...260 V AC / 1-phase (L1/N)
180...260 V AC / 3-phase (L1, L2, L3)
DC-Supply 250...370 V DC (++, --)
Terminal strip X1A / 400 V - Class
suitable for
305...500 V AC / 3-phase (L1, L2, L3)
DC-Supply 420...720 V DC (++, --)
Absolutely observe the connecting voltage of the KEB COMBIVERT. A 230V-unit
will be immediately destructed on a 400V-power supply.
Never exchange the mains and motor cables.
Some countries demand that the PE-terminal is directly connected to the terminal
box (not over the mounting plate).
W
V
U
PB
--
++
L3
N/L2
L1
T1
T2
W
V
U
PB
--
++
L3
L2
L1
T1
T2
++, PB Braking resistor
U, V, W Motor
T1, T2 Temperature sensor / switch (see chapter 3.3.6)
3.3.2 Wiring instructions

Other manuals for KEB COMBIVERT F5 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 Series and is the answer not in the manual?

KEB COMBIVERT F5 Series Specifications

General IconGeneral
BrandKEB
ModelCOMBIVERT F5 Series
CategoryDC Drives
LanguageEnglish

Related product manuals