46
Operation of the Unit
Error
ENTER
F/R
With ENTER only the error message in the display is reset. In order to reset the error itself,
the cause must be removed or a power-on reset must be made.
If a malfunction occurs during operation, the actual display is overwritten by the alarm
message. The alarm message in the display is reset by ENTER.
4.2.2 Resetting error messages
4.2.3 Password input
The KEB COMBIVERT is outfitted with a comprehensive password protection. In
dependence on the entered password the following modes are possible.
Display Mode
CP_ro End customer menu (CP-Parameter) read-only
CP_on End customer menu (CP-Parameter) read/write
CP_SE Service menu (like end customer menu, but with the original parameters )
APPL Application menu (all parameter groups and parameters are visible)
ohne Drive mode (COMBIVERT can be put into operation by the keyboard )
The menu admissible for the application is defined by the machine builder. The password
input is generally made over the parameter CP.0. The adjusted password/menu is
maintained even after switching off.
Password
FUNC
ENTER
UP
Example: Changing the CP-parameter from read-only to read/write