EasyManuals Logo

Kohler 11RMY Service Manual

Kohler 11RMY
98 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
TP-5867 11/02 15Section 2 Scheduled Maintenance
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
160
-- 12.2
-- 6 . 7
-- 1 . 1
4.4
10
21.1
26.7
32.2
37.8
43.3
48.9
54.4
60.0
65.6
71.1
15.6
+ .032
+ .030
+ .028
+ .026
+ .024
+ .022
+ .020
+ .018
+ .016
+ .014
+ .012
+ .010
+ .008
+ .006
+ .004
+ .002
0
-- .002
-- .004
--. 006
-- .008
-- .010
-- .012
-- .014
-- .016
-- .018
-- .020
-- .022
-- .024
-- .026
-- .028
°C °F
Example 1:
Temperature below 26.7
°C(80° F)
Hydrometer Reading 1.250
Electrolyte Temperature
--6.7
°C(20° F)
Subtract .024 Specific Gravity
Corrected Specific Gravity is 1.226
Example 2:
Temperature above 26.7
°C(80° F)
Hydrometer Reading 1.235
Electrolyte Temperature
37.8
°C (100°F)
Add .008 Specific Gravity
Corrected Specific Gravity is
1.243
The temperature correction amounts to about .004 (4 points) of
specific gravity for each 5.5°C(10°F) change in electrolyte
temperature.
Correction
5810322
Figure 2-14 Specific Gravity Temperature Correction
2.8 Storage Procedure
Perform the following storage procedure before taking a
generator set out of service for three months or longer.
Follow the engine manufacturer’s recommendations, if
available, for fuel system and internal engine
component storage.
2.8.1 Lubricating System
Prepare the engine lubricating system for storage as
follows:
1. Run the generator set for a minimum of 30 minutes
to bring it to normal operating temperature.
2. Stop the generator set.
3. With the engine still warm, drain the oil from the
crankcase.
4. Remove and replace the oil filter.
5. Refill the crankcase with oil suited to the climate.
6. Run the generator set for two minutes to distribute
the clean oil.
7. Stop the generator set.
8. Check the oil level and adjust, if needed.
2.8.2 Fuel System
Prepare the fuel system for storage as follows:
1. Start the generator set.
2. With the generator set running, shut off the gas
supply.
3. Run the generator set until the engine stops.
4. Place the generator set master switch in the
OFF/RESET position.

Table of Contents

Other manuals for Kohler 11RMY

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler 11RMY and is the answer not in the manual?

Kohler 11RMY Specifications

General IconGeneral
BrandKohler
Model11RMY
CategoryPortable Generator
LanguageEnglish

Related product manuals