TP-5594 5/95 Scheduled Maintenance 3-17
Wattage Requirements
If the rated capacity of the generator is exceeded, the
circuit breaker(s) located in the controller will trip to
protect the generator against damage. This could be
caused by a short in the AC circuit in the vehicle or
simply by having too many appliances (or tools) turned
onat thesametime resultinginan overload condition. If
the circuit breaker(s) trip, the set may continue running
but there will be no AC output to the protected circuit.
Before resetting the circuit breaker(s), turn off some of
the appliances (or tools) and lights inside the vehicle to
bring the load down within the rated limits of the set. If
this is done and the circuit breaker(s) trips again after
beingreset,ashortcircuitisindicated. Inthisevent,turn
off the set and have a qualified electrician locate and
correct the cause of the short circuit.
The average wattage requirements of some common
RV/Mobileappliances/toolsandmotorloadsarelistedin
the following charts. Use these figures to calculate the
total load on your set to avoid the inconvenience of
having the circuit breaker trip due to overload. The
lighting load is easilydetermined by adding the wattage
rating of each bulb in the circuit. Check the nameplate
ratingonmotorsandappliancesinyourvehicleforexact
wattage requirements.
Electrical Appliance Rating (Watts)
Blanket 50-250. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Blender 600. .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Broiler 1350. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan, Air Circulating 25-100. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fan, Furnace 270. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heater, Space 750-1500. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Heater, Water 1500. . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pan, Frying 1200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Percolator, Coffee 650. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Radio 50-100. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Television 300-750. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Toaster 750-1200. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Figure 3-18. Appliance Average
Wattage Ratings
Air Compressor (Small) 1500 725
Air Compressor 3/4 hp 4000+ 2000
Drill, 1/4 in. 500 250
Drill, 3/8 in. 600 350
Drill, 1/2 in. 800 600
Grinder 1/2 hp 1500 1200
Hammer, Demolition 2000 1800
Hammer, HD Rotary 1500 1200
Paint Sprayer (Airless) 400 240
Polisher, Orbit 500 360
Power Paint Roller 120 90
Power Plane 600 450
Router 900 700
Saw, Circular 6 1/2 in. 2200 1000
Saw, Circular 7 1/4 in. 2500 1200
Saw, Table 10 in. 4000 1500
Saw, Sabre (Worm Drive) 2500 1200
Sander, Belt 1500 600
Sander, Finishing 900 360
Screwdriver, Power 1000 530
Shear, 12 gauge 1800 720
Soldering Gun — 250
Vacuum Cleaner, Wet/Dry 1500 1260
Wrench, Impact 1/2 in. 2000 840
Motor
Starting
Watts
Running
Watts
Construction Tools
Figure 3-19. Construction Tool Average
Wattage Ratings.
NOTE
Motor driven equipmentgenerally takes 2 to 3 timesthe
listed running amperage or wattage to start the motor.
Always check the tool or motor nameplate to be sure.