TP-5594 5/953-18 Scheduled Maintenance
Generator Service
General
Under normal conditions, generator service will not be
requiredon aregularbasis. Ifoperatingunder dustyand
dirtyconditions, usedrycompressedairtoblowdustout
of the generator at frequent intervals. Do this with the
generator set operating and direct the stream of air in
through the cooling slots at the end of the generator.
Storage Procedure
If your generator set is to be out of service for a
considerablelengthoftime(2monthsor more), perform
thefollowingstepstopreservethesetbeforeplacingitin
storage.
1. Drain the oil (while hot) from the crankcase then
refill with regular grade oil. See Section 3, Oil
Selection in this manual.
2. Drain the fuel from the fuel tank to prevent
accumulated moisture from mixing with the fuel.
3. Check the engine coolant protection. See Section
3, Cooling System for additional information.
4. Disconnect battery (negative lead first) and place
in storage.
5. Seal all openingsin the enginewith non-absorbent
adhesive tape. Mask off all areas to be used for
electrical contact.
6. Clean exterior surface of the generator. Spread a
light film of oil over unpainted metallic surfaces
which could rust or corrode.