154 Section 8 Component Testing and Adjustment TP-6356 4/12
Test Method 5
Test coolant temperature faults using a 5 kOhm, 10-
turn, 3-watt potentiometer (part no. X-6136-36), 47 ohm
1/2-watt resistor, and 22 kOhm 1/2-watt resistor using
the illustration shown in Figure 8-58. Before starting the
generator set, turn the potentiometer fully
counterclockwise. While the generator set is running,
turn the potentiometer clockwise until the unit shuts
down.
22 kOhm
Resistor
47 Ohm
Resistor
B
A
SB616
BLK
BRN/ORG,
GRN/WHT
Wiring Harness
Connector
Terminals
5kOhm
Pot.
Figure 8-58 Coolant Temperature Test
Test Method 6
Test coolant temperature faults using a 500 ohm, 10-
turn, 3-watt potentiometer (part no. X-6136-37) and a
1.1 kOhm 1/2-watt resistor, using the illustration shown
in Figure 8-59. Turn potentiometer fully
counterclockwise before starting the generator set to
simulate a low coolant temperature warning. While the
generator set is running, turn the potentiometer
clockwise until the unit shuts down.
SB616
A
B
BLK, 461,
B6--Pin 1
PNK, TAN, 914,
B6--Pin 2
Wiring Harness
Connector Terminals
500 Ohm
Pot.
1.1 kOhm
Resistor
Figure 8-59 Coolant Temperature Test
Test Method 7
This procedure allows testing for overspeed on
DD/MTU-powered models with MDEC or ADEC engine
controls and equipped with a Decision-Makerr 550 or
6000 controller. Use the following procedure to unlock
Menu 20—Factory Setup and perform the overspeed
test. Before using this test method, upgrade the
application software to version 2.47 or higher if not
already installed.
1. Go to Menu 20—Factory Setup
2. Arrow down to the FINAL ASSEMBLY CLOCK NO.
display. Record the clock number on the controller
display.
3. Arrow right to ENTER CODE display.
4. Use the controller keypad to enter the clock number
previously recorded and press ENTER.
5. Arrow down to TEST OVERSPEED SHUTDOWN?
6. Press the YES key and press ENTER.
7. After testing is complete, lock Menu 20 using the
following steps.
8. Go the Menu 20—Factory Setup.
9. Arrow down to the SETUP LOCK display.
10. Press the YES key lock the setup and prevent
alternations to Menu 20—Factory Setup.
Figure 8-61 provides the Decision-Makerr 550 and
6000 controller factory settings for warning and
shutdown faults.
Engine setpoints are also available in Menu 2, Engine
Monitoring with Decision-Makerr 550 and 6000
controllers.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 6000 and is the answer not in the manual?

Kohler Decision-Maker 6000 Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 6000
CategoryPortable Generator
LanguageEnglish

Related product manuals