EasyManuals Logo
Home>Kohler>Portable Generator>Decision-Maker 6000

Kohler Decision-Maker 6000 User Manual

Kohler Decision-Maker 6000
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #207 background imageLoading...
Page #207 background image
207Section 10 Governor AdjustmentsTP-6356 4/12
10.8 Parameter Default Settings
No. Parameter Name Load Share Only
Default Settings
GM17644-4 GM17644-5 GM17644-6
1 No. of flywheel teeth 0 0 0
2 Set Speed A (Hz) 1000 1000 25
3 Set Speed B (Hz) Yes -- 1000 --
4a Idle Speed (Hz) 500 -- 20
4b Idle Speed (Hz) Yes -- 500 --
5 Proportional 1 1 1
6 Integral 0 0 0
7 Derivative 0 0 0
8 OVG @ Set Speed A (gain potentiometer) Yes -- 20 --
9 OVG @ Set Speed B Ye s -- 20 --
10 OVG @ Idle 20 20 20
11 Gain Factor 1 1 1
12 Speed Filter 16 16 4
13 Idle Hold Time (sec.) 0 0 0
14 Accel Rate (Hz/sec.) 1000 1000 3000
15 Decel Rate (Hz/sec.) 1000 1000 3000
16 Startup Rate (Hz/sec.) 1000 1000 3000
17 Startup Limit Yes -- 1000 --
18 Torque Limit Yes -- 1000 --
19 Integral Low Limit 0 0 0
20 Integral High Limit 99 99 99
21 % Droop Yes -- 0 --
22 No Load Calibration Ye s -- 0 --
23 Full Load Calibration Yes -- 1000 --
24 Password 0 0 0
25 Overspeed limit (Hz) 6000 6000 450
26 Set Speed A Min. (Hz) 1000 1000 25
27 Set Speed A Max. (Hz) 5000 5000 300
28 Set Speed B Min. (Hz) Yes -- 1000 --
29 Set Speed B Max. (Hz) Yes -- 5000 --
30 Idle Speed Min. (Hz) 500 500 20
31 Idle Speed Max. (Hz) 5000 5000 300
32 Duty Cycle Limit 10 10 10
33 Startup Speed (Hz) 1000 1000 25
34 Startup Duty Cycle 5 5 5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kohler Decision-Maker 6000 and is the answer not in the manual?

Kohler Decision-Maker 6000 Specifications

General IconGeneral
BrandKohler
ModelDecision-Maker 6000
CategoryPortable Generator
LanguageEnglish

Related product manuals