90 Section 5 Decision-Makerr 550 Controller TP-6356 4/12
Status Event
or Fault
User-Defined
Settings
Time
Delay
(sec.)
Inhibit
Time
Delay
(sec.)
Default
Selection
Range Setting
Relay
Driver
Output
(RDO)
Digital Display
Refer
to
Menu
Overcrank Shutdown 8, 10 OVER CRANK RDO-02
(lead 12)
0--6 Cycles 3 Cycles
Overcurrent 10 OVER
CURRENT
110% 10 Not adjustable
Over Current VR
(voltage restraint)
Shutdownw
10 SD OVER
CURRENT VR
Not adjustable
Overfrequency
Shutdown
7, 10 OVER
FREQUENCY
RDO-28 102%--140% 110% Std.
103% FAA
10
Over Power
Shutdown w
10 SD OVER
POWER
102% Stdby
112% Prime
Not adjustable
Overspeed Shutdown 7, 10 OVER SPEED RDO-01
(lead 39)
65--70 Hz (60 Hz)
55--70 Hz (50 Hz)
70 (60 Hz)
70 (50 Hz)
0.25
Overvoltage
Shutdown
7, 8,
10
OVER
VOL TAGE
RDO-20
(lead 26)
105%--135%
of nominal
115%
2-sec time
delay[
135%
10-sec time
delayw
2--10
Password
(see Access Code)
—
Pre Lube Relay ]
10 PRE LUBE
RELAY
RDO-26 ]
4 Not adjustable
Remote Reset
(see D16)
—
Remote Shutdown
(see D15)
—
Reverse Power
Shutdown w
10 SD REVERSE
POWER
Not adjustable
Speed Sensor Fault 10 SPEED
SENSOR
FAULT
RDO-24 Not adjustable
Starting Aid (see
Time Delay Starting
Aid)
—
System Ready 10 RDO-17
(lead 60)
Not adjustable
Time Delay Engine
Cooldown (TDEC)
8, 10 DELAY ENG
COOLDOWN
RDO-16
(lead 70C)
00:00--10:00
min:sec
5:00
Time Delay Engine
Start (TDES)
8, 10 DELAY ENG
START
00:00--5:00
min:sec
00:01
Time Delay Starting
Aid
8, 10 0--10 sec.
Underfrequency 7, 10 UNDER
FREQUENCY
RDO-29 ]
80%--97% 97% FAA
90%[
80%w
10
Undervoltage
Shutdown
7, 8,
10
UNDER
VOL TAGE
RDO-27 70%--95% 85%
10-sec time
delay[
70%
30-sec time
delayw
5--30
Variable Speed
Governor (VSG) (see
A06)
—
VAR/PF Mode
(see D17)
—
* All models, except Waukesha-powered models. ** NFPA applications
[ Non-paralleling applications [[ DDC/MTU engine with MDEC/ADEC
] Waukesha-powered models ]] FAA only
w Paralleling applications