58 TP-7091 4/23
Note:
For Models 14RCA(L): If the generator set is equipped with a carburetor heater, obtain kit GM102228-S to replace the breather
tube, air cleaner spacer, and gaskets before installing the breather tube and oil heaters.
If the generator set is equipped with a carburetor heater, remove it before installing the breather tube and oil heaters.
The breather tube heating element wraps around the breather tube from the engine to the air cleaner.
Before installing the oil heater kit, drain the oil from the engine. Insert the oil heater near the oil drain valve using the coupling
provided in the kit. Connect the oil heater power cord to the breather tube heater cord.
Figure 54 Oil Heater, Typical
5.7.3 Fuel Regulator Heater (20 and 26 kW models only)
An optional fuel regulator heater is recommended for models 20RCA/L and 26RCA/L for improved cold starting in locations
where the ambient temperature drops below -18°C (0°F). The heater requires a continuous source of AC power.