6 Operation
30 of 88
BoosterControl Advanced
6.4.7 Displaying status information
Measured values are updated every second. Measurements are taken more rapidly,
however.
Displaying general information
General information on operation is displayed at the top menu level.
Select parameter 1-1.
The following information can be displayed:
Table23: Status information 1
Parameter Description Possible values
1-1-1 Actual system pressure measured by BoosterControl
Advanced
0 ... 10000 kPa
1-1-2 Display system load (all pumps in operation) 0 ... 100 %
1-1-3 RDP switch (dry running protection) Available
Not available
1-1-4 Inlet pressure -100 ... 10000 kPa
1-1-5 Level in inlet tank 0 ... 100 %
1-1-6 Level in inlet tank 0 ... 9999 cm
1-1-7 If temperature sensor available:
Display of measured ambient temperature
0 ... 100 °C
1-1-8 Display of status of digital inputs (only from service
access level)
0 enabled
1 disabled
1-1-9 Position of supply valve Open
Closed
Displaying information on pumps connected
Select parameter 1-2.
The following information can be displayed:
Table24: Status information 2
Parameter Description Possible values
1-2-1 Operating status of a pump Automatic
Manual ON (10 s fixed)
Manual OFF
1-2-2 Pump load 0 ... 100 %
1-2-3 Motor protection 0 not tripped
1 tripped
1-2-4 Pump operating hours Days Hours: Minutes
1-2-5 Number of pump starts per pump: Pump: Starts
Displaying statistics
Select parameter 1-3.
The following information can be displayed:
Parameter description
Table25: Status information 3
Parameter Description
1-3-1 Operating hours of system (hours:minutes)
1-3-2 Time to next service
1-3-3 Actual min. runtime of pump