8 Commissioning/Start-up/Shutdown
38 of 88
BoosterControl Advanced
Table30: Parameter settings for cascade control – with jockey pump
Parameter Description Possible values
3-2-2-6 Operating mode Hyamat K
3-3-1 Number of pumps connected
BoosterControl Advanced reboots; observe notes
1 ... 6
3-3-3 Configuration, discharge side
BoosterControl Advanced reboots; observe notes
1 x jockey pump
2 x jockey pump
3-4-2-3 Number of pumps started up in the event of a sensor
failure on the discharge side
0 ... 6
3-4-2-4 Limitation of the maximum system load Number of pumps in operation × 100
%
3-5-1 System pressure setpoint 0 ... x kPa
5)
3-5-3 Bandwidth: range above and below the setpoint
where pumps are not stopped or started
0 … 1000 kPa
3-5-5 Maximum setpoint 0 … x kPa
5)
3-6-2 Limit for minimum runtime of pump 0 … 999 s
3-6-4 Maximum pump runtime. After this period,
BoosterControl Advanced starts the pump with the
least operating hours
0 … 356400 s
3-6-5 When one pump is running: start delay of each
pump that cuts in
0 … 999 s
3-6-6 When more than one pump is running: stop delay of
the pumps
0 … 999 s
8.4.3 Control with one frequency inverter (per system)
The operating mode must be set depending on the frequency inverter used. One
frequency inverter can be firmly assigned to a specific pump or used consecutively for
several pumps (depending on the electrical connection).
Parameter settings can only be made at the service or factory access level.
5) x depends on the maximum value of the pressure sensor used.