8 Commissioning/Start-up/Shutdown
37 of 88
BoosterControl Advanced
Parameter Description Possible values
3-6-4 Maximum pump runtime. After this period,
BoosterControl Advanced starts the pump with the
least operating hours
0 ... 604 800 s (corresponds to 7 days)
3-6-5 When one pump is running: start delay of each
pump that cuts in
0 ... 999 s
3-6-6 When more than one pump is running: stop delay of
the pumps
0 ... 999 s
8.4.2 Cascade control - with jockey pump
Fig.8: Cascade control with jockey pump
1 Bandwidth
H Head
Q Flow rate
S Setpoint
Parameter settings can only be made at the service or factory access level. In the
operating mode with jockey pump, the jockey pump is operated as a base-load pump
at first. If the pressure generated is insufficient, the jockey pump is also started up
again as the last pump.
ü The system is operational.
ü BoosterControl Advanced has been connected correctly.
ü The jockey pump has been sufficiently sized for base-load conditions.
ü Date and time have been set. (ðSection8.3.2,Page34)
1. Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
2. Set the parameters for the suction side. (ðSection8.5.1,Page45)
3. Set the frequency inverter parameters. (ðSection8.4.6,Page44)
4. Note dry running protection settings. (ðSection8.5.1,Page45)
5. Set the following parameters: