EasyManuals Logo
Home>KSB>Controller>BoosterControl Advanced

KSB BoosterControl Advanced User Manual

KSB BoosterControl Advanced
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
8 Commissioning/Start-up/Shutdown
45 of 88
BoosterControl Advanced
Table34: Frequency inverter parameter settings for control with one frequency inverter
Parameter Description Possible values
3-4-3-1 Communication protocol of frequency inverter None
Analog 0 - 20 mA
Analog 4 - 20 mA
PumpDrive
Danfoss MicroDrive
Danfoss VLT2800
Danfoss AquaDrive
3-4-3-2 Proportional constant of PID controller 0...100
3-4-3-3 Integral constant of PID controller 0...60s
3-4-3-4 Differential constant of PID controller
12)
0...99s
3-4-3-9 Start ramp of frequency inverters 0 ... 999 s
3-4-3-10 Stop ramp of frequency inverters 0 ... 999 s
3-4-3-11 Minimum frequency of frequency inverters 0 ... 50 Hz
3-4-3-12 Maximum frequency of frequency inverters 0 ... 50 Hz (60 Hz for Danfoss
MicroDrive)
3-4-3-15 Nominal frequency of frequency inverters 0 ... 50 Hz
8.5 Application functions
BoosterControl Advanced has many useful features that are described in this section:
8.5.1 Setting the parameters for dry running protection
Table35: Parameter settings for dry running protection
Parameter Description Default Possible values
3-3-2 Configuration of suction side
BoosterControl Advanced reboots; observe notes
Setting of suction-side pressure transmitter
- Pressure switch
Pressure sensor
Flow monitoring
3-4-1-1 Calibrate suction-side pressure sensor at 4mA 0 kPa -1 ... 99,99 Bar
3-4-1-2 Calibrate suction-side pressure sensor at 20 mA 1000 kPa 0 ... 99,99 Bar
3-4-2-1 Calibrate discharge-side pressure sensor at 4mA - -1...99,99 Bar
3-4-2-2 Calibrate discharge-side pressure sensor at 20 mA - 0...99,99 Bar
3-5-15 Minimum pressure before dry running protection is
activated
- 0 ... 1000 kPa
3-5-16 Minimum pressure before system restarts after
having been tripped by dry running protection
device
- 0 ... 1000 kPa
3-6-8 Stop delay for system tripped by dry running
protection device
- 0 ... 10 s
3-9 Deactivate the "No water" message in the field list
(then the fault is self-acknowledging)
- -
If a pressure switch is used as a dry running protection device, also set the following
parameters.
8.5.2 Setting an alternative setpoint
If a second setpoint is required at certain times, an alternative setpoint can be set.
The alternative setpoint can be activated either once a day or once a week. Non-
relevant parameters are automatically hidden.
12) The differential constant is always zero.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KSB BoosterControl Advanced and is the answer not in the manual?

KSB BoosterControl Advanced Specifications

General IconGeneral
BrandKSB
ModelBoosterControl Advanced
CategoryController
LanguageEnglish

Related product manuals