8 Commissioning/Start-up/Shutdown
44 of 88
BoosterControl Advanced
Parameter Description
MPO = multiple pump operation
Possible values
3-4-3-5-2 Interval for flow measurement ("0" deactivates the
function)
0-60 s
3-4-3-5-3 Step height for detecting the zero flow 1..100%
3-4-3-5-4 Measuring interval 1...99s
3-4-5-1 High load profile Linear
Cubic
3-4-5-2 Rated frequency 45...50 Hz
3-4-5-3 Start frequency Note 31 ... 50 Hz (3-4-3-12)
3-4-5-4 Stop frequency Note 30 ... 49 Hz 31 ... 50 Hz (3-4-3-11)
3-4-5-5-1 Start power 0...100 kW
3-4-5-5-2 Stop power 0...100 kW
3-4-5-7-1 Rated motor power 0...110
3-4-5-7-2 Rated motor speed 300...3600
3-4-5-7-3 Rated frequency 45 ... 50 Hz (note parameter 3-4-3-12)
3-4-5-7-4 Rated current 0,1....999 A
3-4-5-7-5 Rated cosine phi 0,1...0,99
3-4-5-8-1 Rated pump speed 300...3600
3-5-1 System pressure setpoint 0 ... x kPa
10)11)
3-5-3 Pressure bandwidth: range above and below the
setpoint where pumps are not stopped or started.
Permissible symmetrical deviation from the setpoint.
0 ... 1000 kPa
3-5-5 Maximum setpoint 0 ... x kPa
10)11)
3-6-4 Maximum pump runtime. After this period,
BoosterControl Advanced starts the pump with the
least operating hours
0 ... 356400 s
3-6-5 Time window in which the next pump may be
started up after the previous pump is started up.
0 ... 999 s
3-6-6 Time window in which the next pump may be
stopped after the previous pump is stopped.
0 ... 999 s
8.4.6 Setting the frequency inverter parameters
Parameter settings can only be made at the service or factory access level.
Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
The menu at parameter 3-4-3 only appears if an operating mode with frequency
inverter has been selected at parameter 3-3-3.
The fault reporting relay of the frequency inverter(s) to has been connected correctly
to BoosterControl Advanced.
Setting the bus addresses for the frequency inverters (does not apply to "floating
frequency inverter" operating mode)
If the frequency inverter does not support any bus protocol, please refer to the
manufacturer's instructions. If more than one frequency inverter is used, the bus
addresses must be assigned manually.
Observe the documentation provided by the manufacturer of the frequency inverter.
Setting additional frequency inverter parameters
Set the following parameters:
10) x depends on the maximum value of the pressure sensor used.
11) Dependent on the frequency inverter used (Hyamat VP with PumpDrive)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KSB BoosterControl Advanced and is the answer not in the manual?

KSB BoosterControl Advanced Specifications

General IconGeneral
BrandKSB
ModelBoosterControl Advanced
CategoryController
LanguageEnglish

Related product manuals