10 Parameter list
BoosterControl Advanced
57 of 88
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
1-1-16 WSD pulses tank 3
Water flow detection, number of fills in
tank3
0 - - - Everybody Nobody
1-2 Pumps
Pump-relevant status information
- - - - Everybody Nobody
1-2-1 Operating mode
Setting the operating mode for each
individual pump
- - - - Everybody Everybody
1-2-1.1.1 Pump number
Entering the pump number for which the
operating mode is configured
1 1.. 3 1 3 Everybody Everybody
1-2-1.2.1 Operating mode
Displaying the operating status of the
pump
1 Automatic,
Manual On (10 s),
Manual Off
- - Everybody Everybody
1-2-2 Pump load
Displaying the pump load
- - - - Everybody Nobody
1-2-3 Thermal fail. flags
Bit-based display of status of all thermal
fault inputs
- Not tripped
Tripped
- - Service Nobody
1-2-4 Running hours pump
Displaying the operating hours per pump
- - - - Everybody Nobody
1-2-5 Number of pumpstarts
Displaying the number of starts per pump
- - - - Customer Nobody
1-3 Time and statistics
Operating times and statistics
- - - - Everybody Nobody
1-3-1 Act runtime Op hours
Operating hours of the system
0 - - - Everybody Nobody
1-3-2 Time to service
Time to next service interval
0 - - - Everybody Nobody
1-3-3 Act Minimum Runtime
Current minimum pump runtime in
seconds
- - - - Everybody Nobody
2 Diagnosis
Monitoring and diagnosis
- - - - Everybody Nobody
2-1 General
General monitoring functions
- - - - Everybody Nobody
2-1-1 Active Messages
Current messages for all available
warnings/alerts
- - - - Everybody Customer
2-1-2 History
History of all warnings/alerts
- - - - Everybody Nobody
2-1-3 Acknowledge All
All messages are acknowledged
- - - - Everybody Everybody