Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-3-5 Leakage detection
Activating leakage monitoring
Off On,
off
- - Everybody Service
3-3-6 MPO Functionality
Synchronous operation
Off Off,
On
- - Service Service
3-3-7 PumpMode int/ext
Setting for pump mode via HMI (internal)
or switch (external)
Internal Internal,
external
- - Everybody Service
3-4 System settings
Parameterisation of system
- - - - Everybody Nobody
3-4-1 Inlet
Suction-side parameterisation
- - - - Everybody Nobody
3-4-1-1 Sensor press. 4 mA
Analog measured value at 4mA, suction
side
0 -100.. 1000 -100 1000 Everybody Service
3-4-1-2 Sensor press. 20 mA
Analog measured value at 20 mA, suction
side
1000 0.. 9999 0 9999 Everybody Service
3-4-1-3 Damp. Time Inlet
Damping time for smoothing measured
value to compensate for measurement
peaks
200 100.. 2000 100 2000 Factory Factory
3-4-1-4 Level config
Configuring inlet tank control
- - - - Everybody Service
3-4-1-4-1 0% level
Minimum water level at which no air enters
into tank, in percent, from upper edge of
inlet nozzle
0 0.. 99 0 99 Everybody Service
3-4-1-4-2 100% level
Maximum water level of inlet tank, in
percent, from upper edge of inlet nozzle
200 0.. 999 0 999 Everybody Service
3-4-1-4-3 Sensor level
Distance of sensor positioned above tank
floor to tank floor, in centimetres
0 -100.. 999 -100 999 Everybody Service
3-4-1-4-4 Low level shut down
System stop when dry running level
reached
10 0.. 99 0 99 Everybody Service
3-4-1-4-5 Low level reset
Resetting the system when defined dry
running level is reached
15 0.. 99 0 99 Everybody Service
3-4-1-4-6 Critical water level
Threshold of critical water level in inlet tank
30 0.. 99 0 99 Everybody Service
3-4-1-4-7 High water level
Threshold of high water level in inlet tank
105 0.. 199 0 199 Everybody Service

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KSB BoosterControl Advanced and is the answer not in the manual?

KSB BoosterControl Advanced Specifications

General IconGeneral
BrandKSB
ModelBoosterControl Advanced
CategoryController
LanguageEnglish

Related product manuals