10 Parameter list
74 of 88
BoosterControl Advanced
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-11-2 direct off
Energy-saving mode is carried out without
zero-flow detection function
Off Off,
On
- - Service Service
3-11-3 Power down speed %
Calculated stop speed if zero-flow
detection is activated in energy-saving
mode (in %).
30 1.. 99 1 99 Service Service
3-11-4 time direct off
Time after which the energy-saving mode
is carried out without the zero-flow
detection function
5 0.. 9999 0 9999 Service Service
3-12 FC failure behavior
Frequency inverter fault behaviour
- - - - Everybody Service
3-12-1 behavior
Behaviour
Off Off,
cascade (without
frequency inverter)
- - Service Service
3-12-2 Fixed Speed
Cascade (without frequency inverter)
- - - - Service Nobody
3-12-2-1 Max power
Limitation of maximum system power (n x
100%, n = number of pumps)
300 0.. 600 0 600 Service Service
3-12-2-2 Set point
Entering the pressure setpoint (system
pressure)
400 0.. 1000 0 1000 Service Customer
3-12-2-3 Bandwidth
Bandwidth
30 0.. 999 0 999 Service Customer
3-12-2-4 Min. run time
Limit for minimum runtime of pump
30 0.. 999 0 999 Service Customer
3-12-2-5 Max. run time
Maximum pump runtime. After the time
has lapsed, the system switches over to
the next pump.
86400 0.. 356400 0 356400 Service Service
3-12-2-6 Start delay
Start delay of pumps if pressure remains
below setpoint.
2 0.. 999 0 999 Service Service
3-13 Pump Changeover
Pump changeover
- - - - Everybody Service
3-13-1 Supply reaction
Selection of oversupply/undersupply
Undersupply Undersupply,
oversupply
- - Everybody Service
3-13-2 Changeover delay
Time delay between pump changeover
0 0.. 10 0 10 Everybody Service
3-14 By Pass Valve
Bypass valve
- - - - Everybody Service

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KSB BoosterControl Advanced and is the answer not in the manual?

KSB BoosterControl Advanced Specifications

General IconGeneral
BrandKSB
ModelBoosterControl Advanced
CategoryController
LanguageEnglish

Related product manuals