@ (hexa) @ (deci) DS50
01H 1 R/W L [On / Off] Unit 3111
02H 2 R/W L [Reset] Discharges the safety measures of the unit 3112
03H 3 R/W L [Enable] Stopping and running of the Fan Blower.[Off] the blower is stopped, 3351
[On] the blower is running. (BMS)
04H 4 R/W L [Enable] Stopping and running of the fan in the "Control Dead Zone". 3352
[Off] the blower is stopped, [On] the blower is running. (BMS)
05H 5 R/W L [BMS] Activation of the Inoccupation mode [Off] occupation mode - 3933
[On] inoccupation mode
06H 6 R/W L [Room regulation] Choices of the priority of regulation in Heating -
[Off] Heat Pump then Hot water coil or Electric or Gas 3324
[On] Hot water coil or Electric or Gas then Heat Pump (BMS)
07H 7 R/W L [F-Air Reheat] Activate reheating of the fresh air in the dead zone 3331
to maintain supply temperature. (BMS)
08H 8 R/W L [F-Air Reheat] Choices of the priority of regulation in Heating -
[Off] Heat Pump then Hot water coil or Electric or Gas 3332
[On] Hot water coil or Electric or Gas then Heat Pump (BMS)
09H 9 R/W L [Enable] Run eco: [On] the Economiser is running, [Off] the Economiser if stopped. 3353
(BMS)
0AH 10 R/W L [Enable] Run CO2 Sensor: [On] Switch-on the CO2 control on a Zone, 3354
[Off] Stop the CO2 control on a zone. (BMS)
0BH 11 R/W L [Enable] [OFF] Force the unloading of compressors in cooling mode. 3355
(BMS)
0CH 12 R/W L [Enable] [OFF] Force the unloading of compressors in heating mode. 3356
(BMS)
0DH 13 R/W L [Enable] [OFF] Force the unloading of heating module (electric, gas or heat water coil) 3357
(BMS)
0EH 14 R/W L [Enable] [OFF] Force the unloading of humidity control. 3358
(BMS)
0FH 15 R/W L not used
10H 16 R/W L [Clock] [OFF] read hour & minute [ON] write hour & minute …
R = Read
W = Write
L = Logical
ELECTRICAL DATA - CONTROL variables
MODBUS
Settings and Readings