from Firmware V06.00 - DMS 1.1 EN - 11/2011 L 23
8400 StateLine C | Operating instructions
Before commissioning
General notes on applications
5.3.1 Select control mode
Different control modes can be selected for every application in C00007. By selecting the
control mode you set the way the technology application should be controlled, e.g. via
terminals or via a fieldbus.
C00007
Pre-assignment of the digital terminals in the control modes "Terminals 0/2/11/16"
The four control modes "Terminals 0/2/11/16" only differ in the assignment of the digital
terminals to the control inputs of the application:
Control mode
Selection list (Lenze setting printed in bold) Info
0 Wiring has changed This display appears if the FB interconnection has been
changed in the preconfigured I/O interconnection.
10 Terminals 0 The technology application is controlled via the digital
and analog input terminals of the controller.
For a short overview of the preconfigured terminal
assignment, see the following segment.
12 Terminals 2
14 Terminals 11
16 Terminal 16
20 Keypad The technology application is controlled via the keypad.
21 PC See software manual.
30 CAN
40 MCI
Control mode "Terminals 0": Control mode "Terminals 2":
Control mode "Terminals 11": Control mode "Terminals 16":
X4
DI3
DI2
DI4
DO1
GIO
24I
DI1
RFR
24E
+
=
DriveReady
Controller enable / reset error
External supply 24 V DC
Fixed setpoint 1/3
Fixed setpoint 2/3
DC brake
Change of direction of rotation
+
=
X4
DI3
DI2
DI4
GIO
24I
DI1
RFR
24E
+
DO1
Controller enable / reset error
Fixed setpoint 1/3
Fixed setpoint 2/3
Change of direction of rotation
Quickstop
DriveReady
External supply 24 V DC
+
=
+
X4
DI3
DI2
DI4
GIO
24I
DI1
RFR
24E
+
DO1
Controller enable / reset error
Change of direction of rotation
DC brake active
Speed higher
Speed lower
Motor potentiometer
DriveReady
External supply 24 V DC
+
=
X4
DI3
DI2
DI4
GIO
24I
DI1
RFR
24E
+
DO1
Controller enable / reset error
Fixed setpoint 1/3
Fixed setpoint 2/3
Cw rotation quick stop
Ccw rotation quick stop
DriveReady
External supply 24 V DC