8400 StateLine C | Operating instructions
Commissioning
Adapting the most important parameters to the drive task
34 L from Firmware V06.00 - DMS 1.1 EN - 11/2011
6.3 Adapting the most important parameters to the drive task
The following short overview contains the most important parameters for a quick
commissioning.
The following subchapters provide more detailed information on these parameters.
A description of all parameters
can be found in the software manual of the controller
and in the Engineer online help.
Parameter Name Info/Lenze setting
Basic settings
C00011 Appl.: Reference speed 1500 rpm
C00059 Appl.: Reference frequency C11 -
C00015 VFC: V/f base frequency 50.0 Hz VFC = Voltage Frequency Control
C00016 VFC: Vmin boost 1.60 %
C00022 Imax in motor mode depending on the device power
C00120 Setting of motor overload (I²xt) 100.00 %
C00142 Auto-start option 0x19 ≡ Controller inhibit when
• the controller is switched on (device on)
•Undervoltage
• Loading of the Lenze setting
C00173 Mains voltage 0: "3ph 400V / 1ph 230V"
Application parameters
C00034/1 AIN1: Configuration 0: "-10...+10 v" AIN1 = analog input
C00026/1 AIN1: Offset 0.00 %
C00027/1 AIN1: Gain 1.0000
C00010/x AIN1: Characteristic see parameter description
C00012 Acceleration time - main setpoint 2.000 s
C00013 Deceleration time - main setpoint 2.000 s
C00039/1 Fixed setpoint 1 40.00 %
C00039/2 Fixed setpoint 2 60.00 %
C00039/3 Fixed setpoint 3 80.00 %
C00105 Decel. time - quick stop 2.000 s
C00114 DIx: Polarity No inversion DIx = digital inputs
C00118 DOx: Polarity No inversion DOx = digital outputs
C00434/1 O1U: Gain 100.00 % O1U = analog output
(voltage output)
C00435/1 O1U: Offset 0.00 %
Motor control
C00006 Motor control 6: "VFCplus:V /f linear"
C00018 Switching frequency 2: "8 kHz var./drive-opt."
C00021 Slip compensation 2.67 %
C00019 Auto-DCB: Threshold 3 rpm DCB = DC-injection braking
C00036 DC braking: Current 50.00 %
C00106 Auto DCB: Hold time 0.500 s
C00910/1 Max. pos. output frequency 1000 Hz
C00910/2 Max. neg. output frequency 1000 Hz
Highlighted in grey = display parameter