8400 StateLine C | Operating instructions
Commissioning
Quick commissioning with the keypad
28 L from Firmware V06.00 - DMS 1.1 EN - 11/2011
6.2 Quick commissioning with the keypad
Target:
For test and demonstration purposes, the load-free motor shall be rotated in best
time with an amount of wiring as little as possible and few settings.
Control via terminals or keypad?
For this simple application, you can choose between two drive control options:
Terminal control (default setting):
– A setpoint potentiometer connected to the analog voltage input of the controller
serves as speed setpoint source.
– The control signals are selected via the digital inputs of the controller.
Keypad control:
– The speed setpoint is selected with the keypad via C00728/3.
– The control signals are selected with the keypad via C00727/1...5.
Required commissioning steps
1. Wiring of power and control terminals.
– Refer to the mounting instructions supplied with the drive controller to find help on
how to correctly design the power connections to match the requirements of your
device.
– A wiring example can be found in the chapter "Connection/wiring of the controller
".
( 12)
– For keypad control, only terminal X4/RFR of the control terminals (for controller
enable) must be wired:
2. Inhibit controller: Set terminal X4/RFR to LOW level or open contact.
3. Switch on voltage supply of the controller.
– Without motor operation
: Connect external 24 V supply.
– With motor operation
: Connect mains voltage.
If the green "DRV-RDY" LED is blinking and the red "DRV-ERR" LED is off, the controller
is ready for operation and commissioning can proceed.
4. Load Lenze setting to controller.
This step is recommended to get a defined device configuration. All parameter settings
in the controller are reset to the Lenze setting.
Digital terminals (X4) Name Function
RFR HIGH level Controller enable
HIGHÌLOW Reset error message
LOW level
(or open)
Controller inhibit
(
,