from Firmware V06.00 - DMS 1.1 EN - 11/2011 L 49
8400 StateLine C | Operating instructions
Diagnostics & troubleshooting
Error messages
7.5 Error messages
Error message Cause Remedies
An01: AIN1_I < 4 mA Open-circuit monitoring for analog input 1
has tripped.
Only if the analog input has been
configured as a current loop of
4 ... 20 (C00034/1 = 2).
Check wiring of the analog X3/A1I
input terminal for open circuit.
Check minimum current values of the
signal sources.
Ck16: Time overflow manual control Manual PC control: The connection
monitoring has tripped.
The online connection between the PC
and the controller has been interrupted
for a longer period of time than the
timeout set in C00464/1.
Check the communication link
between the PC and the controller.
Check the voltage supply/function of
the controller.
Adjust the timeout (C00464/1).
dF10: AutoTrip Reset Too frequent auto-trip reset. Check the error cause that activates the
auto-trip reset.
Eliminate error cause and reset
(acknowledge) error manually
afterwards.
dF14: SW/HW invalid Device error Consultation with Lenze required.
dF18: BU RCOM error
dF21: BU Watchdog
dF22: CU watchdog
dF25: CU RCOM error Mains switching too frequent.
Cyclic mains switching every 3 min is
permissible.
After switching the mains 3 times in
one minute, there must be a switching
pause of 9 min.
If the problem occurs again, you needs
to consult Lenze.
dF50: Retain error An error has occurred when accessing
retain data.
Either caused by an internal hardware
error or by lack of mains switching after
a firmware download.
Mains switching
If the problem occurs again, you needs
to consult Lenze.
dH09: EEPROM power section Device error Consultation with Lenze required.
dH10: Fan failure The device fan has failed.
Possible causes:
The short-circuit check of the fan
connection has tripped.
The speed monitoring of the fan has
tripped.
Check the fan for short-circuit.
•Clean the fan.
dH68: Adjustment data error CU Device error Consultation with Lenze required.
dH69: Adjustment data error BU
FC1: Field controller limitation The output of the field controller has
reached its maximum limit value. The
drive is at the torque limit in the field
weakening range.
Observe load requirements.
Correct dimensioning or reduce
setpoint from the field weakening
range if necessary.
FCH1: Switching frequency reduction Load-dependent switching frequency
reduction
Observe load requirements.
Correct dimensioning or reduce
setpoint generation dynamics if
necessary.
FCH2: Max. speed for Fchop Maximum speed for chopper frequency
has been reached.
The maximum speed has been
exceeded depending on the switching
frequency.
Select the correct maximum speed as a
function of the switching frequency.