System description
SaCoS
one
GENSET
This document is property of MAN Diesel & Turbo SE and is entrusted
to whom it has been handed over. Copying and communicating to third
parties is only permitted with written consent of MAN Diesel & Turbo!
SaCoSone.GENSET_System description_m_en_V1.5.docx
Remote speed setting is either possible via 4-20mA signal or by using hardwired lower/raise
commands.
Speed adjustment range
Between -5% and +10% of the nominal speed at idle running.
Droop
Adjustable by parameterisation tool from 0-5% droop.
Load distribution
By droop setting.
Engine stop
Engine stop can be initiated local at the display module and remote via a hardware channel or
the bus interface.