SaCoSone.GENSET_Communication_m_en_1.7
3.3 Data Format
Example for Modbus ASCII Data Format:
Extract from Modbus ASCII list
Signal fault ZS82 : Emergency stop
(pushbutton)
Signal fault ZS75 : Turning gear
disengaged
Signal fault SS84 : Remote stop
Signal fault SS83 : Remote start
Signal fault LAH28 : Lube oil level
high
Signal fault LAL28 : Lube oil level
low
Signal fault LAH42 : Fuel oil leakage
high
Signal fault ZS97 : Remote switch
Signal fault LAH92 : OMD alarm
Signal fault TAH 29-27 : CCMON
alarm
Signal fault : Remote reset
Signal fault LAH98 : Alternator
cooling water leakage alarm
Signal fault : Emergency generator
mode
Signal fault : Speed raise
Signal fault : Speed lower
Signal fault : Switch isochronous /
droop mode
For this example we assume that the following alarms have been triggered:
Signal fault SS83 : Remote start,
Signal fault LAL28 : Lube oil level low,
Signal fault ZS97 : Remote switch,
Signal fault LAH92 : OMD alarm,
Signal fault TAH 29-27 : CCMON alarm,
Signal fault : Emergency generator mode,
Signal fault : Switch isochronous / droop mode
The Bit-sample of MW 113:
In Modbus ASCII these 16 Bits are grouped in 4 groups each containing 4
Bits and then translated from binary format to hexadecimal format (0-9, A-F)