3.2 Data Machinery Interface
This interface serves for data exchange to ship alarm systems or integrated automation
systems (IAS).
The status messages, alarms and safety actions, which are generated in the system, can be
transferred. All measuring values and alarms acquired by SaCoS
one
GENSET are available for
transfer.
The following MODBUS protocols are available:
MODBUS RTU (Standard)
MODBUS ASCII (for retrofits)
For a detailed description of these protocols see the document “SaCoS
one
GENSET,
Communication from the GenSet”.
3.3 Generator Control
SaCoS
one
provides inputs for all temperature signals for the temperatures of the generator
bearings and generator windings.
3.4 Power Management
Hardwired interface for remote start/stop, speed setting, alternator circuit breaker trip etc.
3.5 Remote control
For remote control several digital inputs are available.
3.6 Ethernet interface
The Ethernet interface at the Display Module can be used for the connection of SaCoS
one
EXPERT.
3.7 Serial interface
CoCoS-EDS can be connected to a serial RS485 interface.
3.8 Power supply
The plant has to provide electric power for the automation and monitoring system. In general a
redundant, uninterrupted 24V DC (+20% -30% and max ripple 10%) power supply is required
for SaCoS
one
.
The alarm system requires a 24V DC, 12,5 A uninterrupted power supply with a 16 A pre-fuse.
The safety system requires a 24V DC, 8,5 A uninterrupted power supply with a 10 A pre-fuse.