V6R VRF 50Hz
104
Midea
V6R
Series Service Manual
2.13 H2, H3: Qty. of outdoor unit decreases/ increases error
Digital display output
Description
ï‚§ H2 indicates Qty. of outdoor unit decreases error.
ï‚§ H3 indicates Qty. of outdoor unit increases error.
ï‚§ All units stop running.
ï‚§ Error code is only displayed on the master unit.
Trigger / recover condition
ï‚§ Trigger condition: Qty. of slave units detected by master unit has decreased or increased.
ï‚§ Recover condition: Qty. of slave units detected by master unit goes back to normal.
ï‚§ Reset method: Resume automatically.
Possible causes
ï‚§ Some outdoor units are powered off.
ï‚§ Power supply abnormal.
ï‚§ Incorrect outdoor unit address setting.
ï‚§ Communication wires between outdoor units not connected properly.
ï‚§ Loosened wiring within electric control box.
ï‚§ Damaged outdoor main PCB or electric control box communication terminals block.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6R VRF Series and is the answer not in the manual?

Midea V6R VRF Series Specifications

General IconGeneral
BrandMidea
ModelV6R VRF Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals