Midea
V6R
Series Service Manual
The capacity set on switch ENC2 on the
outdoor main PCB and the capacity given
on the unit’s nameplate do not match
Ensure the setting on switch ENC2
matches the unit capacity given on the
unit’s nameplate
Some power wires or communication
wires of fan module are not connected
properly
Ensure power and communication wires
are connected properly
The fan motor is blocked or has failed
Remove obstruction or replace the fan
motor
The power supply is abnormal
Check the power supply equipment
Replace the fan module resolves the
error
Replace the outdoor main PCB