EasyManuals Logo
Home>Midea>Air Conditioner>V6R VRF Series

Midea V6R VRF Series User Manual

Midea V6R VRF Series
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #127 background imageLoading...
Page #127 background image
V6R VRF 50Hz
126
Midea
V6R
Series Service Manual
2.20 P2, H5: Suction pipe low pressure protection
Description
ï‚§ All units stop running.
ï‚§ Error code is displayed on the unit with the error.
Trigger / recover condition
ï‚§ Trigger condition:
For P2 protection: Suction pressure < 0.07MPa.
For H5 protection: P2 protection appears three times in 60 minutes.
ï‚§ Recover condition:
 Cooling Only/Main Cooling Discharge pressure ≥ 0.23MPa and Restart permission=ON.
 Heating Only/Main Heating Discharge pressure ≥ 0.18MPa and Restart permission=ON.
ï‚§ Reset method:
For P2 protection: Resume automatically.
For H5 protection: Manually restart.
Possible causes
ï‚§ Outdoor unit stop valves are closed.
ï‚§ Insufficient refrigerant.
ï‚§ Low pressure side blockage.
ï‚§ Poor evaporator heat exchange.
ï‚§ Outdoor main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6R VRF Series and is the answer not in the manual?

Midea V6R VRF Series Specifications

General IconGeneral
BrandMidea
ModelV6R VRF Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals