Figure 3-6.4: Low pressure protection control in heating operation
Notes:
1. P
e
: Suction pressure
6.3 Discharge Temperature Protection Control
This control protects the compressors from abnormally high temperatures and transient spikes in temperature. It is
performed for each compressor.
Figure 3-6.5: Discharge temperature protection control
Notes:
1. T7C1: Compressor discharge temperature
When the discharge temperature rises above 115°C the system displays P4 protection and all units stop running. When P4
protection occurs 3 times in 100 minutes, the H6 error is displayed. When an H6 error occurs, a manual system restart is
required before the system can resume operation.
6.4 Over-current Protection Control
Over current protection control is performed to prevent tripping due to transient inverter over-current. It protects the
compressors from abnormally high currents. It is performed for each compressor.
Figure 3-6.6: Over-current protection control
Table 3-6.1: Current limitation for compressor inverter modules
Notes:
1. The current limitation value is the actual current * 4
Low pressure protection, error code P2 is displayed
When P2 protection occurs 3 times in
60 minutes, the H5 error is displayed.
When an H5 error occurs, a manual
system restart is required before the
system can resume operation.
Discharge temperature protection, error code P4 is displayed
Over current protection, error code P3 is displayed