2.17 Hb: Low pressure sensor error
Digital display output
Description
ï‚§ Low pressure sensor error.
ï‚§ All units stop running.
ï‚§ Error code is displayed on the unit with the error.
Trigger / recover condition
ï‚§ Trigger condition: The main control board cannot receive the feedback signal of low pressure sensor.
ï‚§ Recover condition: The main control board can receive the feedback signal of low pressure sensor.
ï‚§ Reset method: Resume automatically.
Possible causes
ï‚§ Outdoor unit Low gas stop valves are closed.
ï‚§ Pressure sensor not connected properly or has malfunction.
ï‚§ Outdoor main PCB damaged.