36.0 Telephone Operation
1. When any telephone zone rings (the local buzzer sounds intermittently, and the green
zone LED and Incoming Call LED flash) press that zone's button (on the selector panel
QAZT-5302DS) once to answer. Once any one zone has been answered, calls from any
other zone will cause that zone's green LED and the Incoming Call LED at the master
telephone to flash and the buzzer will sound.
2. Press the answered zone's button once again to hang up. (Note that the telephone zone
will hang up automatically if all handsets on the zone are placed back on the hook).
36.1 QMT-5302N and QMT-5302NV Master Telephone LEDs
Trouble LED
This LED will flash amber if there is any zone or other trouble in the firefighters' telephone
system.
Incoming Call LED
This LED will flash green if any telephone zone has a handset off-hook and unanswered. It will
illuminate steady green if all telephone zones with off-hook handsets have been answered.
Call Control Active LED
This LED will illuminate when there is a connection between the designated Master Telephone
(at the CACF) and the present QMT-5302N or QMT-5302NV telephone.
36.2 QMT-5302N and QMT-5302NV Master Telephone Pushbutton Controls
Call Control
Pressing this pushbutton will connect this master telephone with master telephones as
configured.
Deselect All
Pressing this pushbutton will disconnect all master telephone calls initiated at this node (Call
Control minus).
36.3 QAZT-5348DS and QAZT-5302DS Network Firefighters’ Telephone
Selector Panel LEDs
Telephone Zone Green LED
This LED will flash green if there is any handset off-hook on that zone, and the zone has not
been answered by pressing the zone's button. Once answered, the LED will be steady green.
Telephone Zone Amber LED
This LED will flash amber to indicate trouble on open-circuit zone faults (e.g. missing end-of-
line resistor or wire breaks) or short-circuit zone faults.
36.4 QAZT-5348DS and QAZT-5302DS Network Firefighters’ Telephone
Selector Panel Pushbutton Controls
Telephone Selection Pushbutton
Pressing the telephone selector pushbutton will select the associated telephone to be
connected to the Master Telephone. Pressing this button a second time will hang up.

Table of Contents

Other manuals for Mircom FleXNet FX-4000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mircom FleXNet FX-4000 and is the answer not in the manual?

Mircom FleXNet FX-4000 Specifications

General IconGeneral
BrandMircom
ModelFleXNet FX-4000
CategoryMeasuring Instruments
LanguageEnglish