• External static pressure table
How to interpret the blower characteristics table
Example : Case of FDUMA252R
2-spot blowout.....................
Internal resistance increases more than
the standard 3-spot blowout.Approx.
14Pa at 17m
3
/min
Square duct blowout...........
Internal resistance decreases more than
the standard round duct (ø200 3-spot).
3Pa at 17m
3
/min. (External static
pressure increases in reverse.)
Model
Duct specs.
1 spot
closing
Standard
Stan-
dard
High
speed
(4)
Stan-
dard
High
(4)
speed
Stan-
dard
High
speed
(1)
Square duct
Air flow
(m
3
/min)
FDUMA252
FDUMA302
FDUMA402
FDUMA502,602
14
18
20
28
34
-
35
30
50
50
-
70
65
80
75
50
50
50
60
60
85
85
85
90
85
50
55
55
65
65
90
90
90
95
95
FDUMA202
Unit : Pa
40
20
0
–20
1413 16 18 20
–10
Static pressure (Pa)
Air flow (m
3
/min)
3-spot blower
internal resistance
Standar
High
Standard
Medium
Standard Lo
Square duct blower
internal resistance
2-spot blower
internal resistance
3-spot blower
internal resistance
Standard
High
Standard
Medium
Standard Low
internal resistance
2-spot blower
internal resistance
FDUMA252R
13 14 18 20
100
120
20
0
-10
-20
80
60
40
Air flow(m
3
/min)
Lower
limit
16
Static pressure (Pa)
High speed
·Upper lim
it
Standard·Upper limit
High speed·Low limit
High speed·High
High speed·Medium
High speed·Low
Standard·Low
Standard·Medium
Standard·High
FDUMA202R
100
120
80
60
40
20
0
-20
10 12 14 15.5
Air flow(m
3
/min)
Lower
limit
Upper
limit
[Standard]
2-spot blower internal resistance
Square duct blower internal resistance
High speed·
Upper limit
Standard·Upper limit
High speed·Low limit
High speed·High
High speed·Medium
High speed·
Low
Standard·Low
Standard·Medium
Standard·High
Static pressure (Pa)
[Standard]
3-spot blower internal resistance
2-spot blower internal resistance
Square duct blower internal resistance
Uppe
limit
Notes (1) 1 spot closing: Round duct flange at center is removed and shield with a
special panel (option).
(2) Standard: ø200 duct are installed at all blowout holes.
(3) Square duct: All round ducts are removed and replaced with special
square duct flanges (option).
(4) When using the high speed setting, turn the dip switch SW9-4 on the
indoor PCB to the ON position.
(When setting from the remote controller, select “Hi CEILNG 1”)