48
-
(3) Correction of cooling and heating capacity in relation to one way length of refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
(2) Correction of cooling and heating capacity in relation to air flow rate control (fan speed)
Coefficient: 1.00 at High, 0.95 at Low
Item
Hi 0.056 0.063 0.043
Air flow Me 0.041 0.048 0.034
Lo 0.028 0.034 0.025
Model
FDKNA151, 201 FDKNA251 FDKNA301
Model FDKN type
Item
Hi 0.111 0.053 0.069 0.106 0.050
Air flow
Lo 0.083 0.037 0.049 0.079 0.034
Model
FDURA201 FDURA251 FDURA301 FDURA401 FDURA501
Model FDUR type
Note (1) Calculate the equivalent length using the following formula.
However, install the piping so that the equivalent length is within +5 m of the piping distance limit )actual length) for each respective piping system.
• Equivalent Length = Actual Length + (equivalent length of bends x number of bends in the piping)
Models FDCA301~601
Equivalent piping length
(1)
m 7.5 10 15 20 25 30 35 40 45 50 55
Heating 1 0.995 0.992 0.990 0.987 0.984 0.981 0.978 0.975 0.972 0.970
FDCA301 model 1 0.996 0.989 0.982 0.974 0.967 0.959 0.952 0.945 0.937 0.930
FDCA401 model 1 0.995 0.986 0.976 0.967 0.957 0.948 0.938 0.929 0.919 0.910
FDCA501 model 1 0.994 0.982 0.969 0.957 0.945 0.933 0.921 0.908 0.896 0.884
FDCA601 model 1 0.993 0.978 0.963 0.948 0.933 0.918 0.903 0.888 0.873 0.858
Cooling
Models FDCA801, 1001
Equivalent piping length
(1)
m 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75
Heating 1 0.998 0.992 0.986 0.980 0.974 0.968 0.962 0.956 0.951 0.945 0.939 0.933 0.927 0.921
FDCA801 model 1 0.997 0.984 0.972 0.960 0.949 0.937 0.926 0.916 0.906 0.896 0.886 0.877 0.869 0.860
FDCA1001 model 1 0.998 0.995 0.991 0.988 0.984 0.981 0.977 0.974 0.970 0.967 0.963 0.960 0.956 0.953
Cooling
Capacity compensation
coefficient
Gas piping length (m)
Cooling
Cooling
Heating
(801)
(1001)
020406080
1.05
1.00
0.95
0.90
0.85
0.80
0.75
Equivalent Length for 1 Bend
ø12.7
0.200.15
ø9.52 ø15.88
0.25
ø19.05
0.30
ø25.4
0.40
Gas Pipe Diameter (mm)
Bend Equivalent Length