187
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
7 Basic Instruction
7.4 OR, ORI
1
Introduction
2
Overview
3
Instruction
List
4
Devices
in Detail
5
Specified the
Device &
Constant
6
Before
Programming
7
Basic
Instruction
8
FNC00-FNC09
Program Flow
9
FNC10-FNC19
Move & Compare
10
FNC20-FNC29
Arith. & Logic
Operation
5. Bit specification of data register (D)
*1
A bit in data register (D) can be specified as a device used in OR and ORI instructions.
When specifying a bit in data register, input "."
after a data register (D) number, and then input a
bit number (0 to F) consecutively.
Only 16-bit data registers are available.
Specify a bit number as "0, 1, 2, ... 9, A, B, ... F"
from the least significant bit.
Example: In the example shown on the left, OR
contact is set to ON (becomes
conductive) or OFF (becomes non-
conductive) by bit 3 of D0.
*1. This function is supported only in FX
3U
/FX3UC PLCs.
Errors
When an I/O number used in OR or ORI instruction does not exist due to indexing, M8316 (Non-existing I/O
specification error) turns ON.
When the device number of a device (M, T or C) other than I/O used in OR or ORI instruction does not exist due to
indexing, an operation error (error code: 6706) occurs.
Circuit program List program
LD
OR
OUT
0000
0001
0004
X000
D0.3
Y000
Y000
D0.3
X000

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U Series
CategoryController
LanguageEnglish

Related product manuals