695
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
31 Data Transfer 3 – FNC276 to FNC279
31.1 FNC278 – RBFM / Divided BFM Read
31
FNC276-FNC279
Data
Transfer 3
32
FNC280-FNC289
High-Speed
Processing 2
33
FNC290-FNC299
Extension File
Register
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
Program example
In the example shown below, data is read from and written to the buffer memories (BFM) in the unit No. 2 as follows
:
When X000 is set to ON, data stored in D100 to D179 (80 points) are written to the buffer memories (BFM) #1001
to 1080 in the special function block/unit whose unit number is No. 2 by 16 points in each operation cycle.
When X001 is set to ON, the buffer memories (BFM) #2001 to 2080 (80 points) in the special function block/unit
whose unit number is No. 2 are written to D200 to D279 by 16 points in each operation cycle.
X000
SET M0
The BFM write start flag is set
to ON.
FNC279
WBFM
K2 K1001 D100 K80 K16
BFM write
start
M0
BFM write
start
M8029
Instruction execution complete
RST M0
M8329
Instruction execution
abnormally complete
RST M0
X001
SET M5
BFM read
start
FNC278
RBFM
K2 K2001 D200 K80 K16
M5
BFM read
start
M8029
Instruction execution complete
RST M5
M8329
Instruction execution
abnormally complete
RST M5
END
D100 to D179 (80 points) are written to
the buffer memories #1001 to 1080 in
the unit No. 2 (in 5 operation cycles).
The BFM write start flag is set to OFF.
Execution of the WBFM instruction is
waited.
The BFM write start flag is set to OFF.
The BFM read start flag is set to ON.
The buffer memories #2001 to 2080 (80
points) in the unit No. 2 are read to
D200 to D279 (in 5 operation cycles).
The BFM read start flag is set to OFF.
The BFM read start flag is set to OFF.
M8328
Y000
Instruction non-execution
Execution of the RBFM instruction is
waited.
M8328
Y001
Instruction non-execution

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U Series
CategoryController
LanguageEnglish

Related product manuals