893
FX3G/FX3U/FX3GC/FX3UC Series
Programming Manual - Basic & Applied Instruction Edition
A Programming Tool Applicability and Version Upgrade History
A-1 Programming Tool Applicability
31
FNC276-FNC279
Data
Transfer 3
32
FNC280-FNC289
High-Speed
Processing 2
33
FNC290-FNC299
Extension File
Register
34
FNC300-FNC305
FX
3U
-CF-ADP
35
SFC•STL
Programming
36
Interrupt
Function
37
Special Device
38
Error Code
A
Version Up
Information
B
Execution Times
Item Caution
Circuit blooks which require attention on
operation after writing during RUN
During RUN, avoid writing to a circuit block including the following instructions under execution. If
writing is executed during RUN to such a circuit block, the PLC decelerates and stops pulse output.
DSZR (FNC150), DVIT (FNC151), ZRN (FNC156), PLSV (FNC157) instructions [with
acceleration/deceleration operation], DRVI (FNC158) and/or DRVA (FNC159) instructions
During RUN, avoid writing to a circuit block including the following instruction under execution. If
writing is executed during RUN to such a circuit block, the PLC immediately stops pulse output.
PLSV (FNC157) instruction [without acceleration/deceleration operation]
During RUN, avoid writing to a circuit block including the following instructions under execution of
communication. If writing is executed during RUN to such a circuit block, the PLC may stop
communication after that.
If the PLC stops communication, set the PLC to the STOP mode once, and then set it to the RUN
mode again.
IVCK (FNC270), IVDR (FNC271), IVRD (FNC272), IVWR (FNC273), IVBWR (FNC274) and IVMC
(FNC275) instructions
During RUN, avoid writing to a circuit block including the following instruction under execution.
If such writing is executed during RUN, instructions being executed are canceled.
FLCRT (FNC300), FLDEL (FNC301), FLWR (FNC302), FLRD (FNC303),
FLCMD (FNC304) and FLSTRD (FNC305) instructions
When writing to a circuit block during RUN, which includes the following instructions, the following
results.
instruction for falling edge pulse
When writing is completed during RUN for a circuit including an instruction for falling edge pulse
(LDF, ANDF, or ORF instruction), the instruction for falling edge pulse is not executed regardless
of the ON/OFF status of the target device of the instruction for falling edge pulse.
When writing is completed during RUN for a circuit including an instruction for falling edge pulse
(PLF instruction), the instruction for falling edge pulse is not executed regardless of the ON/OFF
status of the operation condition device.
It is necessary to set to ON the target device or operation condition device once and then set it to
OFF to execute the instruction for falling edge pulse.
Instruction for rising edge pulse
When writing is completed during RUN for a circuit including an instruction for rising edge pulse,
the instruction for rising edge pulse is executed if a target device of the instruction for rising edge
pulse or the operation condition device is ON.
Target instructions for rising edge pulse: LDP, ANDP, ORP, and pulse operation type applied
instructions (such as MOVP)
*1. The PLS instruction is not executed.
When writing to a circuit block during RUN, which includes the following instructions, the following
results.
Pulse instruction during rising edge of operation results (MEP instruction)
After writing to the circuit with MEP instructions during RUN, the MEP instruction result turns ON
(conductive) while the operation results leading up to the MEP instruction are ON.
Pulse instruction during falling edge of operation results (MEF instruction)
After writing to the circuit with MEF instructions during RUN, the MEF instruction result turns OFF
(non-conductive), regardless of the operation results up to the MEF instruction.
The operation results of the MEF instruction turns ON (conductive) when the operation results
leading up to the MEF instruction are turned OFF.
Other
When GX Works2 Ver. 1.08J or later or GX Developer Ver. 8.18U or later is used in FX
3U/FX3UC
PLCs to write data during RUN, the following will occur.
If the number of program steps is reduced by deleting contact or coil application instructions, etc.,
the program becomes shorter by the number of reduced steps.
When GX Works2 Ver. 1.08J or later or GX Developer Ver. 8.72A or later is used in FX3G/FX3GC
PLCs to write data during RUN, the following will occur.
If the number of program steps is reduced by deleting contact or coil application instructions, etc.,
the program becomes shorter by the number of reduced steps.
•FX3U/FX3UC PLCs Ver. 3.00 or later and GX Works2 Ver. 1.62Q or later.
Writing during RUN is enabled only when the protection status (valid or invalid) by the setting
"Read-protect the execution program" for the block password is same as the protection status of
the PLC designated as the target of writing during RUN.
While writing is executed during RUN
Instruction for rising
edge pulse
Instruction for falling
edge pulse
OFF Not executed Not executed
ON
Executed
*1
Not executed
Operation results leading up to MEP/MEF
instruction
MEP instruction MEF instruction
OFF
OFF
(non-conductive)
OFF
(non-conductive)
ON
ON
(conductive)
OFF
(non-conductive)

Table of Contents

Other manuals for Mitsubishi FX3U Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX3U Series and is the answer not in the manual?

Mitsubishi FX3U Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX3U Series
CategoryController
LanguageEnglish

Related product manuals