3 - 26 3 - 26
MELSEC-
A
3 SPECIFICATIONS
3.8 Data Link Processing Time
The CC-Link side data link and CC-Link/LT side data link operate asynchronously.
3.8.1 CC-Link link scan time
Refer to the user's manual of the master module.
3.8.2 CC-Link/LT link scan time
This section explains the CC-Link/LT link scan time.
[Link scan time (LS)]
LS = a + (b
N) c [ s]
a: Constant
b: Constant
c: Constant
N: Last station number
Transmission speed 2.5 Mbps 625 kbps 156 kbps
a 22 88 353
4-point mode 46 41 37
8-point mode 56 51 47
b
16-point mode 76 71 67
c 0.4 1.6 6.4
(ms)Link scan time
Number of
stations
Link scan time
(2.5Mbps when 8 stations (4 occupied stations 2 modules) are occupied)
0
14 28 56
0
0.5
1.0
1.5
2.0
2.5
16-point mode
8-point mode
4-point mode

Table of Contents